MULTI-ENERGY DRIVEN CHILLERS (2D SERIES)

100 TR to 3500 TR

Cooling Capacity

Upto - 5 °C chilled water temp.

Delta T 30° C

Multiple Heat Sources

Thermax multi energy machines are designed as per Single-Double effect technology, enabling maximum heat recovery from both the heat sources. High grade and low grade heat is used in Double effect cycle and Single effect cycle respectively. Most commonly used Multi energy machine is EJ Series i.e., using Engine exhaust and engine jacket water.
Multi Energy Driven Chillers, EJ Series, Multi-Energy like Engine exhaust and engine jacket water, High grade and low grade heat is used in Double effect

Operating Range

Capacities : From 100 to 3500 USRT (175 to 12300kW)

Chilled water temperature : Up to 1ºC (34ºF) and -2ºC (28.5ºF) for brine

Heat source : Exhaust gas, steam, hot water & liquid/gas fuels

High Grade
  • Steam (4 to 10Kg/cm²)
  • Exhaust gas(350 to 600ºC)
  • Hot water(150 to 180ºC)
Low grade
  • Steam( 0 to 3Kg/cm²)
  • Hot water(80 to 95ºC)
Supplementary backup : Direct Oil/Gas Firing

COP : 1.0 – 1.1